D350 GC (60 Hz) Generator Set

D350 GC (60 Hz) Generator Set

360° Exterior View

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

PDF Print Share

Generator Set Specifications

Maximum Rating
350 ekW
Minimum Rating
350 ekW
Emissions/Fuel Strategy
EPA Stationary Emergency
Voltage
480 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby

Engine Specifications

Engine Model
Cat® C13 In-line 6, 4-cycle diesel
Bore
5.1in
Stroke
6.2in
Displacement
763in³
Compression Ratio
16.3:1
Aspiration
Turbocharged Air-to-Air Aftercooled
Fuel System
MEUI
Governor Type
ADEM™A4

Generator Set Dimensions

Length - Maximum
182.8in
Width - Maximum
64.2in
Height - Minimum
80.3in
Height - Maximum
96.7in
Dry Weight - Genset (minimum)
6929.1lb
Dry Weight - Genset (maximum)
7255.4lb

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

M-Frame Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

GCCP 1.2 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to104°F (40°C)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • UL 2200 Listed
  • ULC Certification Available

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment:

Optional Equipment:

    Air Inlet System
    • Air Cleaner (Non-Canister Disposable)
    Bases, Mounting & Fuel Tanks
    • Wide Base - Skid
    • Overfill Prevention Valve
    • 5 gallon Spill Containment
    • Fuel Tank Fill Pipe & Lockable Cap
    • Integral Tank Base, 24 Hrs, UL142
    • Audio & Visual Fuel Alarm (@90% Fuel Level)
    Circuit Breaker
    • 1200A LS/I
    • 800A LSI
    • 400A LS/I
    • Auxiliary Contacts
    • 600A LS/I
    • 600A LSI
    • 1200A LSI
    • 400A LSI
    • 800A LS/I
    Control System
    • Volt Free Contacts
    • Ground Fault Relay
    • Audible Alarm Gp
    • Twist Release, Red Button Emergency Stop
    • 20A GFCI (Ground Fault Circuit Interrupter)
    • 100A Load Center
    • Product Link Remote Monitoring hardware
    • 16 -light NFPA 99/110 Annunciator
    Enclosures
    • E-Stop
    • Sound Attenuated Level 2 Enclosure (White)
    • AC & DC Source Lights
    Exhaust System
    • Flexible Exhaust Connection
    • 8" Muffler - 25 dBA Attenuation
    • Manifold & Turbocharger Guards
    Generator
    • Space Heater
    • Permanent Magnet Generator
    Starting System
    • Battery Charger (UL Certified)
    • Jacket Water Heater
    • Standard Battery Set: 1000 CCA, 90 amp/hr.
    • Oversize Battery Set, 1400 CCA, 200 amp/hr.
    Circuit Breakers
    • Circuit breaker (IEC) auxiliary contacts
    • 4 Pole (IEC-100% rated) circuit breaker - Motorised
    • Shunt trip for IEC circuit breaker
    General
    • Extended Service Coverage
    • UL2200 Certification
    • CSA Certification
    • Generator Test Report
    Starting / Charging System
    • Jacket water heater
    • Battery disconnect switch