C32 Generator Set

C32 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

PDF Print SHARE

Generator Set Specifications

Minimum Rating
910 kVA
Maximum Rating
1500 kVA
Emissions/Fuel Strategy
Low Fuel Consumption, Low Emissions
Voltage
400 to 3300 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Engine Specifications

Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.71in
Stroke
6.38in
Displacement
1958.86in³
Compression Ratio
15.0:1
Aspiration
TA
Fuel System
MEUI
Governor Type
Adem™A4

Generator Set Dimensions

Length - Minimum
164in
Length - Maximum
176.6in
Width - Minimum
66.3in
Width - Maximum
87.8in
Height - Minimum
85.1in
Height - Maximum
86.4in
Dry Weight - Genset (minimum)
14700lb
Dry Weight - Genset (maximum)
17855lb

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets other NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • IBC Seismic Certification
  • EU Certification of Conformance (CE)
  • Eurasian Conformity (EAC)

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment:

Optional Equipment:

    Air Inlet System
    • Standard air cleaner
    • Dual element air cleaner
    • Heavy duty air cleaner
    Circuit Breakers
    • Center posts busbars
    • Shrouds
    • Cable supports
    • Power connection covers
    • Enclosures - Control packaging
    • Circuit breaker wiring groups
    • 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit Breakers
    • 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC Rated Circuit Breakers
    • 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit Breakers
    Control Panels
    • EMCP 4.3, EMCP 4.4
    Cooling System
    • Standard radiator
    • High Ambient radiator
    • Certified radiator
    • Extended life coolant
    • Radiator duct flange
    Exhaust System
    • All C32 engines have 203 mm (8 in) exhaust outlets
    • Guard and Shield System
    • Elbow mounting kit
    • Flanges
    • Flexible fittings
    • Flange and exhaust expanders
    • Mufflers
    • Exhaust through wall kit
    Generator And Attachments
    • Low voltage generators
    • Medium voltage generators
    Lube System
    • Oil level regulator
    • Oil pan
    • Prelube manual sump pump
    Mounting System
    • Standard package isolators
    • Spring type vibration isolator
    • IBC vibration isolators
    • Mounting base types
    Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
    Power Connections
    • Low voltage connection cables
    • Neutral grounding connection
    • Center post busbar
    Starting / Charging System
    • 10 Amp battery charger
    • 10 Amp enclosure battery charger
    • 20 Amp battery charger
    • 35 Amp battery charger
    • Standard 24 volt Open package battery set - Dry
    • Electric starting motor - Standard / Heavy duty
    • Jacket water heater
    • Space heater
    Special Tests / Reports
    • IBC seismic certifications
    • OSHPD seismic certifications
    • CSA test and certification
    • PGS test report @ 1.0 power factor
    • PGS test report @ 0.8 power factor
    • Generator test report
    • Standard engine test
    • Standard genset Torsional Vibration Analysis (TVA) report
    • Custom genset TVA report
    Enclosures
    • Premium sound attenuated enclosure
    • Sound attenuated enclosure
    • Color options
    • Enclosure fuel tank options
    • Enclosure louvres - fixed and motorized
    • Cold weather bundle
    • DC lighting package
    • AC panel, outlets and lights
    • Panel bracket
    General
    • US aid emblem
    • Special paint