Generator Set Specifications

Minimum Rating
680 ekW
Maximum Rating
800 ekW
Voltage
208 to 600
Frequency
60 Hz
Speed
1800 rpm

Generator Set Configurations

Emissions/Fuel Strategy
Low Fuel Consumption, U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 Nonroad Equivalent Emission Standards)

Engine Specifications

Engine Model
C27 ATAAC, V-12, 4-Stroke, Water-Cooled Diesel
Displacement
1649.47in³
Fuel System
MEUI
Aspiration
TA
Governor Type
Adem™A4
Compression Ratio
16.5:1
Bore
5.4in
Stroke
6in

Generator Set Dimensions

Length - Maximum
184in
Width - Maximum
67.8in
Height - Maximum
85.1in

Standard Equipment:

Optional Equipment:

    Air Inlet System
    • Standard air cleaners
    • Dual element air cleaners
    • Heavy duty air cleaners
    Starting / Charging System
    • 10 Amp battery chargers
    • 20 Amp enclosure battery chargers
    • 24 Volt battery sets - Dry
    • 24 Volt electric start motors - Heavy duty
    • Jacket water heaters
    • Air starting motor with control and silencer
    • Space heater
    Circuit Breakers
    • 400, 800, 1200, 1600, 2000, 2500, 3000 Amp, 3 pole, UL-100% rated circuit breakers
    • 2000 Amp, 3 pole, IEC rated circuit breakers
    • 800 Amp, 4 pole, IEC rated circuit breakers
    Control Panels
    • EMCP 4.3, EMCP4.4
    • Remote mounting harness
    • Remote mounted circuit breaker terminals
    • Remote mounted panel harness mounting kit
    • Auxiliary box options
    • Side extension box
    • Cable shroud - Top mounted
    • Cable shroud - Bottom mounted
    • Cat connect telematics
    • Installed DIO module
    • Remote DIO module
    • Annunciator modules
    • Remote annunciator modules
    • Modbus monitor local packages
    • Load share module
    • Vandal proof panel cover
    Cooling System
    • Standard radiator
    • High ambient radiator
    • Certified radiator
    • Extended life coolant
    • Radiator duct flange
    Enclosures
    • Special sound attenuated enclosure
    • Enclosure with lifting base or fuel tank
    • Enclosure fuel tank options
    • Enclosure louvers
    • Cold weather bundle
    • Enclosure lighting
    • AC distribution panel, lights and outlet
    • Panel bracket
    • Enclosure colors
    Exhaust System
    • Flanges
    • Guard and shield system
    • Elbows
    • Flexible fittings
    • Mufflers
    • Exhaust through the wall kit
    Generator And Attachments
    • 60 Hz standard generators
    • 60 Hz premium generators
    Lube System
    • Oil level regulator
    • Prelube pumps
    Mounting System
    • Puck style low efficiency isolators
    • Spring type vibration isolators
    • IBC vibration isolators
    • Mounting base type
    Power Connections
    • Neutral grounding connection
    • Center post busbar
    • Power connections - Right / Left / Rear
    • Cable entry - Right / Left / Rear
    Special Tests / Reports
    • IBC Seismic certifications
    • OSHPD Seismic certifications
    • Special CSA test cerification
    • PGS test report @ 1.0 power factor
    • PGS test report @ 0.8 power factor
    • Generator test report
    • Standard engine test
    • Torsional vibration analysis report
    General
    • Special paint
    • US aid emblem
    • SGS Inspection
    • Miscellaneous inspection