3516C Tier 4 Final

3516C Tier 4 Final

The 3516C HD generator set has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. ...
PDF Print SHARE

Generator Set Specifications

Minimum Rating
1650 ekW
Maximum Rating
2500 ekW
Emissions/Fuel Strategy
U.S. EPA Certified for Non-Emergency Stationary Genset
Voltage
480 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime

Engine Specifications

Engine Model
3516C HD, ATAAC, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69in
Stroke
8.46in
Displacement
78in
Compression Ratio
14.7:1
Aspiration
TA
Fuel System
Electronic unit injection
Governor Type
ADEM™A4

Generator Set Dimensions

Length - Minimum
267.6in
Length - Maximum
277in
Width - Minimum
93.7in
Width - Maximum
101.2in
Height - Minimum
116.7in
Height - Maximum
118.9in
Dry Weight - Genset (minimum)
37200lb
Dry Weight - Genset (maximum)
40280lb

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets other NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
  • Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
  • SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
  • EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
  • Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
  • Certifications

  • UL 2200 Listed
  • CSA Certified
  • IBC seismic certification
  • OSHPD pre-approval

    One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
  • World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
  • Standard Equipment:

    Optional Equipment:

      Control System
      • EMCP 4.3, EMCP 4.4
      Crankcase System
      • No explosion relief valves
      • Explosion relief valves
      • Ventilation system
      Exhaust System
      • Elbows
      • Flange and exhaust expanders
      • Flanges
      • Flexible fittings
      • Y-Adapters
      • Mufflers
      • Exhaust offset
      • Tier 4 clean emissions module
      • Tier 4 dosing cabinet
      • Tier 4 clean emission MOD Kits
      • Clean emission parts
      • Dry exhaust manifold
      • Flanged faced outlet(s)
      Generators And Attachments
      • Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
      • Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
      • High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
      • High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
      • Space heater kits
      • Generator conversion
      • Thermostate for space heater
      • Alternator air cleaner
      • Differential current transformers (DCT)
      • Differntial current transformers (DCT) 8.7 kV and 15 kV classes
      Instrumentation
      • Pyrometer and thermocouples
      Mounting System
      • Puck style low efficiency isolators
      • Spring type vibration isolators
      • IBC vibration isolators
      • Rails - engine/generator/radiator mounting
      • Anti-vibration mounts (shipped loose)
      • Rubber anti-vibration mounts (shipped loose)
      Power Connections
      • Ground cables between generator and terminal box
      • Neutral ground connections
      • Center post busbar
      • Right side power connections
      • Left side power connections
      • Rear power connections
      • 2700 Frame, four lead, four terminal
      • Low voltage circuit breakers
      Special Tests / Reports
      • Canadian Standards Association certification
      • IBC certification
      • OSHPD certification
      • PGS test report @ 1.0 power factor
      • PGS test report @ 0.8 power factor
      • Standard engine test charge
      • generator test report
      • Fuel consumption test
      • Generator set fuel consumption test
      • Torsional vibration analysis reports
      Starting And Charging
      • Engine barring device
      • 24 Volt battery set - Dry
      • 10, 20, 35 and 50 amp battery chargers
      • Electric starting motors
      • Air starting motors
      • Starter cover
      • Air pressure regulator
      • Jacket water heaters
      Extended Service Coverage
      • Platinum, Gold and Silver coverage