DG450 GC (3 phase)

DG450-2 (Single-phase)

THE RUNDOWN

Engine
  • Four-stroke-cycle gas engine combines consistent performance and excellent fuel economy with minimum weight
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency
EMCP Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Design Criteria
  • The generator set facilitates compliance with NFPA 110 and meets ISO 8528-5 requirements for transient response
  • Cooling system designed to operate in 50˚C/122˚F ambient temperatures with an air flow restriction of 0.5 in. water
UL 2200 / CSA - Optional
  • UL 2200 Listed packages
  • CSA Certified
  • Certain restrictions may apply
  • Consult with your Cat® Dealer
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Generator Set Specifications
Frequency60 Hz
Natural Gas Rating450 ekW
Emissions/Fuel StrategyU.S. EPA Certified for Non-Emergency Application
Voltage120/208, 120/240, 277/480, 346/600 VAC
Displacement1336.42in³
Fuel TypeNatural Gas
Speed1800 rpm
Engine Specifications
Engine ModelG21.9L V12, 4-Cycle, Spark -Ignited
Fuel SystemCarburetor, Down Draft
AspirationTurbocharged - Aftercooled
Governor TypeElectronic
Bore5.03in
Stroke5.6in
Compression Ratio10.0:1
Generator Set Dimensions
Length154.4in
Width71in
Height67in
Weight8274lb
Standard Equipment

Cooling

  • Closed coolant recovery system
  • 50/50 Ethylene glycol antifreeze
  • Factory-installed radiator

Fuel

  • Fuel pressure test po
  • Low fuel pressure switch
  • Primary and secondary fuel shut-off

Generator

  • Class H insulation material
  • Permanent magnet excitation
  • Full load capacity alternator

Controls

  • EMCP 4.2 Series generator set controller

Mounting

  • Vibration isolaton (puck type)

Electric Starting and/or Prelube

  • Engine electrical system
  • Battery cables
  • Solenoid activated starter motor

Electric Power - Package Serial Number Prefix

  • Battery charging alternator
Optional Equipment

Generator

  • Thermal magnetic or electronic trip MCCBs
  • Anti-condensation heater
  • Shunt trip and auxiliary contact breaker