C175-20
THE RUNDOWN
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
Cat ECS Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- EU Declaration of Conformity
- EU Declaration of Incorporation
- Eurasian Conformity (EAC)
- IBC seismic certification
One Safe Source
- Components used in the generator set are selected at the design stage to provide optimum package performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Cat® Diesel Engine
- Rugged, durable design with reliable performance proven in thousands of applications worldwide
- Certified alternative fuels including Hydrotreated Vegetable Oil (HVO), Renewable Diesel (RD) and Hydrotreated Renewable Diesel (HRD) which meet EN 15940 or ASTM D975 can be used or blended with EN 590 diesel
Cat Generator Set Package
- Accepts 100% block load in one step
- Meets NFPA 110 loading requirements
- Conforms to ISO 8528-5 G3 load acceptance requirements
- Reliability verified through torsional vibration, fuel consumption, oil consumption, transient performance, and endurance testing
Alternators
- Superior motor starting capability minimizes need for oversizing generator
- Designed to match performance and output characteristics of Cat diesel engines
Cooling System with Radiator
- Cooling systems are available to operate in ambient temperatures up to 50°C (122°F)
- Tested to ensure proper generator set cooling
Cat® Energy Control System (ECS)
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirements
- Expansion modules and site specific programming for specific customer requirements
- Graphical touchscreen display
- Easily upgradeable
Warranty
- 24 months/1000-hour warranty for Standby and Mission Critical ratings
- 12 months/unlimited hour warranty for Prime and Continuous ratings
- 12 months/unlimited hour warranty for Prime-DCP ratings
- Extended service protection is available to provide extended coverage options
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Financing
- Caterpillar offers an array of financial products to help you succeed through financial service excellence
- Options include loans, finance lease, operating lease, working capital, and revolving line of credit
- Contact your local Cat dealer for availability in your region
Generator Set Specifications
| Standby Rating | 4000(no fan)/3900/3350(no fan) kVA |
| Prime Power Rating | 3600(no fan)/3500 kVA |
| Emissions/Fuel Strategy | Low Fuel, Low Emissions |
| Voltage | 400 to 11000 Volts |
| Frequency | 50 Hz |
| Speed | 1500 RPM |
| Duty Cycle | Standby, Mission Critical, Prime, Continuous |
| Maximum Rating | 4000 kVA |
| Minimum Rating | 3150 kVA |
Engine Specifications
| Engine Model | C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel |
| Bore | 6.89in |
| Stroke | 8.66in |
| Displacement | 6456.31in³ |
| Compression Ratio | 15.3:1 |
| Aspiration | Turbo Aftercooled |
| Fuel System | Common Rail |
| Governor Type | ADEM� A4 |
Generator Set Dimensions
| Length - Minimum | 264.2in |
| Length - Maximum | 330.8in |
| Width - Minimum | 85.1in |
| Width - Maximum | 127.8in |
| Height - Minimum | 87.6in |
| Height - Maximum | 150.7in |
| Dry Weight - Genset (minimum) | 55100lb |
| Dry Weight - Genset (maximum) | 66200lb |
Standard Equipment
Air Inlet
- 4 x Single element canister air cleaners with service indicator(s).
Control Panel
- Engine cycle crank
- Oil pressure (psi, kPa or bar)
- Digital Indicators
- Coolant temperature
- Environmental sealed front face
- Frequency (Hz)
- True RMS AC metering, 3-phase, +/-2% accuracy
- Text alarm/event descriptions
- Low coolant level
- Volts (L-L & L-N)
- Auto/start/stop control
- Warning/shutdown Indicators:
- Emergency stop pushbutton
- Engine cool-down timer
- DC volts
- High coolant temperature
- Operating hours
- Low oil pressure
- Cat ECS 100
- Amps (per phase & average)
- 4 Programmable relay Inputs
- Alarm acknowledge
- 4 Programmable relay output
- Failure to start (overcrank)
- Overspeed
- Lamp test
- 24 Volt DC operation
- Wall mounted controls
- RPM
Cooling System
- SCAC cooling
- Coolant sensors
- JW Inlet: 6" ANSI / JW Outlet: 5" Cat Flange
- AC Inlet: 6" ANSI / AC Outlet: 3-1/2" ANSI
Exhaust
- Dry exhaust manifold
- Bolted flange (ANSI 6" & DIN 150) with bellow for each turbo (Qty 4). 50 Hz
Fuel
- Filters x 3
- Secondary/tertiary fuel filters
- 4 Micron spin on type
- 10 Micron spin on type
- Engine mounted filters x 3
- Primary fuel filter water/fuel water separator
Generators and Attachments
- 3 Phase voltage sensing
- Exciter diode monitor
- 6 Leads
- 3 Phase brushless
- Right side extension box, bottom cable entry
- Permanent magnet excitation (PMG)
- Class H temperature rise at 40C ambient
- Salient pole
- RFI suppression
- Anti-condensation space heater
- IEC platinum Stator RTDs
- Form wound
- NEMA Class H insulation
- Voltage regulator
- Reactive droop capability
- Min/max Exciter limiter
Governing System
- ADEM A4
- Redundant shutdown (Overspeed protection through a duplicate speed sensing system)
Lube System
- Oil drain lines and valve
- Gear type lube oil pump
- Oil filter, filler and dipstick
- Integral lube Oil cooler
- Lubricating oil
- Fumes disposal
Mounting Systems
- Rails - Engine/Generator
- Rubber anti-vibration mounts - shipped loose
Starting / Charging System
- Batteries and battery rack w/cables
- Dual 24 volt electric starting motors
- Battery disconnect switch
General
- SAE standard rotation
- Right hand servicing
- Paint - Caterpillar yellow with high gloss black rails
Optional Equipment
Air Inlet Systems
- Single element air cleaner
Control Panels
- EMCP 4.4
- Controller and MV and HV power connection locations
- Load share module
- Controller voltage and current sensing groups
- Speed adjust
- Annunciator modules
- Customer interface options
- Generator temperature monitoring
- E-Stop
- Interconnect harness
- Generator harness
- Modbus monitoring of packages
- Vandal proof panel door
Cooling System
- Package mounted radiators
- Remote radiators
- Fuel cooler
Crankcase Systems
- Explosive relief valves
- Crankcase ventilation system
Exhaust System
- Front housing - Standby or mission critical
- Front housing - Prime or continuous
- Exhaust collectors/manifold
- Mufflers (15, 25 and 34 dBA)
Fuel System
- Primary fuel filter
Generators and Attachments
- Medium voltage - 3000 Frames - 50 Hz, 3 phase, 1500 rpm, FW, PM, No of leads=6, Pitch 0.6667
- Thermostat for space heater
- Generator air cleaner
- Differential current transformers - (5, 9 and 15 kV Class)
Instrumentation
- Pyrometer and thermocouples
Lube System
- Lube oil heater
- Lube oil heater with Crankcase explosion relief valves
- Drain group oil pans
- Lubricating oil
- Electric prelube pumps
- Oil filters
Mounting System
- Rubber anti-vibration mounts
- Spring type linear vibration isolators
- IBC vibration isolators - Shipped loose
Special Tests / Reports
- Generator test report
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
- Standard genset TVA (Torsional Vibration Analysis) report
- Custom generator TVA report
- Special test charge - Engine only
- Genset fuel consumption test
- Standard engine test charge
Starting / Charging System
- 24 Volt electric starting motor
- Air starting motor
- Air pressure regulator
- Starter location covers
- 24 Volt battery set - Dry
- 20, 35 and 50 Amp Battery chargers
- Charging alternators - Dry
- Jacket water heaters
General
- Special paint - 3500, Colors (other than Caterpillar yellow or high performance paints)
- US aid emblem
- Service tools
- Engine barring group
- Manual
- Engine barring air powered
- control GP - air powered bar group