C15 (60 Hz)

C15 Generator Set

THE RUNDOWN

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
UL2200 Listed; CSA 22.2; Certification of Compliance – IBC Seismic; Dual IBC & HCAI
One Safe Source
  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Generator Set Specifications
Maximum Rating500 ekW
Standby Rating350/400/450/500 ekW
Minimum Rating320 ekW
Prime Power Rating320/365/410/455 ekW
Emissions/Fuel StrategyU.S. EPA Tier 3 Certified
Voltage208 to 600 Volts
Frequency60 Hz
Speed1800 RPM
Duty CycleStandby, Prime
Engine Specifications
Engine ModelC15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore5.4in
Stroke6.75in
Displacement927.56in³
Compression Ratio16.1:1
AspirationAir to Air Aftercooled
Fuel SystemMEUI
Governor TypeAdem™A4
Generator Set Dimensions
Length - Maximum168.2in
Width - Maximum81in
Height - Maximum126.3in
Standard Equipment

Air Inlet

  • Air cleaner

Air System

  • Turbocharger
  • Air cleaner - Non canister disposable paper filter
  • Aftercooler core

Control Panel

  • GCCP 1.2
  • GCCP 1.3 Genset Controller

Cooling

  • Package mounted radiator

Cooling System

  • Caterpillar extended life coolant
  • Fan drive, battery charging alternator drive
  • Radiator and cooling fan with guard
  • Coolant drain line with valve

Exhaust

  • Base, formed steel with single wall integral 8-hour fuel tank
  • Standard open set fuel tank/base supplied
  • Exhaust flange outlet

Fuel

  • Secondary fuel filters
  • Primary fuel filter with integral water separator
  • Fuel priming pump

Fuel System

  • Primary fuel filter w/integral water separator and secondary filter
  • Fuel priming pump
  • Narrow skid base
  • Flexible fuel lines
  • Fuel cooler

Generator

  • Matched to the performance and output characteristics of Cat engines
  • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
  • IP23 Protection

Power Termination

  • Busbar

Generator and Attachments

  • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
  • Automatic voltage regulator (AVR)
  • Segregated low voltage (AC/DC) wiring panel
  • Optional LC Frame generator - IP23 Protection
  • Cold weather bundle
  • A Frame generator - IP21 Protection

Mounting

  • Rubber vibration isolators

Governing System

  • Cat electronic governor (ADEM A4).

Lube System

  • Oil cooler
  • Oil drain valves

Mounting System

Telematics

  • Cat® Product Link™ PL444 cellular

Starting/Charging

  • 24 Volt battery with rack and cables
  • 24V Starting motor
  • Standard battery

General

  • Engine and alternator pre paint, Caterpillar yellow
  • Paint - Caterpillar yellow except rails and radiators gloss black
Optional Equipment

Air Inlet System

  • Dual element air cleaner
  • Hevy Duty air cleaner

Exhaust

  • 10 dBA, 25 dBA, SA Level 1 / Level 2 Mufflers

Certifications

  • UL2200, IBC, HCAI
  • Global certification for CIS

Circuit breakers

  • Shunt trip for IEC circuit breaker
  • Padlockable circuit breaker device
  • 4 Pole (IEC-100% rated) Circuit breakers - Motorised
  • Auxiliary contacts, circuit breaker
  • 3 Pole (IEC-100% rated) Circuit breakers - Motorised
  • 3 Pole (IEC-100% rated) Circuit breakers - Package mounted
  • 4 Pole (IEC-100% rated) Circuit breakers - Package mounted
  • Power terminal strip

Generator

  • Oversize and premium generators
  • Anti-condensation heater
  • Excitation: Permanent magnet excitation (PMG), Internally Excited (IE)

Power Termination

  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant

Fuel System

  • Michigan tank kit bundle
  • Integral tanks / Wide base
  • Manual fuel transfer pump
  • Optional BS799 Compliant Integral - Dual wall fuel tank base
  • Fuel transfer system controls

Control Panels

  • GCCP 1.5
  • Load center
  • Local annunciator
  • Remote annunciator module
  • I/O expansion module
  • Oil temperature displays
  • Protective devices: Earth fault relay ; Earth leakage Ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor

Starting/Charging

  • Jacket water heater
  • Charging alternator
  • Heavy duty starting system
  • Battery chargers
  • Oversize batteries

Cooling System

  • Stone guards
  • Radiator duct flange
  • Low coolant temperature alarm

Enclosures

  • Sound attenuated Level 1, Level 2 (Steel/Aluminium)
  • Weather Protective

General

  • Sound attenuated, weather protective or high ambient weather protective enclosure
  • CSA Certification
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • EEC Declaration of Conformity
  • Integral & sub-base UL listed dual wall fuel tanks
  • Automatic transfer switches (ATS)
  • Single or dual wall sub-base fuel tanks
  • The following options are based on regional and product configuration:
  • EU Certificate of Conformance (CE)
  • Single or dual wall integral fuel tanks
  • Narrow, wide or skid base
  • UL 2200 package

Exhaust System

  • Engine mounted muffler
  • 10, 25 dBA, SA Level1 / Level2 mufflers
  • 6 and 8 inch elbow kit
  • Manifold and turbocharger guards
  • Flexible exhaust fittings
  • 6 and 8 inch flange GP

Generator and Attachments

  • Space heaters
  • Permanent magnet excitation (PMG) generator
  • Ingress protection
  • LC frame generator
  • Oversize A Frame generator
  • LC frame CIP generator
  • CIP A Frame generator
  • Oversize LC frame generator

Lube System

  • Manual sump pump

Mounting System

  • Narrow skid base - replaces standard fuel tank base

Special Test / Reports

  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8 power factor

Starting / Charging System

  • 5A Battery charger
  • Battery disconnect switch
  • Jacket water heater