3512B (50 Hz) 1320 -1625 kVA

3512B (50 Hz) Generator Set

THE RUNDOWN

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
Cat ECS Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • IBC seismic certification
  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • EU Eurasian Conformity (EAC)
One Safe Source
  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Cat® Diesel Engine
  • Rugged, durable design with reliable performance proven in thousands of applications worldwide
  • Certified alternative fuels including Hydrotreated Vegetable Oil (HVO), Renewable Diesel (RD) and Hydrotreated Renewable Diesel (HRD) which meet EN 15940 or ASTM D975 can be used or blended with EN 590 diesel
Cat Generator Set Package
  • Accepts 100% block load in one step
  • Meets NFPA 110 loading requirements
  • Conforms to ISO 8528-5 G3 load acceptance requirements
  • Reliability verified through torsional vibration, fuel consumption, oil consumption, transient performance, and endurance testing
Alternators
  • Superior motor starting capability minimizes need for oversizing generator
  • Designed to match performance and output characteristics of Cat diesel engines
Cooling System
  • Cooling systems are available to operate in ambient temperatures up to 50°C (122°F)
  • Tested to ensure proper generator set cooling
Cat® Energy Control System (ECS)
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirements
  • Expansion modules and site specific programming for specific customer requirements
  • Graphical touchscreen display
  • Easily upgradeable
Warranty
  • 24 months/1000-hour warranty for Standby and Mission Critical ratings
  • 12 months/unlimited hour warranty for Prime and Continuous ratings
  • 12 months/unlimited hour warranty for Prime-DCP ratings
  • Extended service protection is available to provide extended coverage options
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Financing
  • Caterpillar offers an array of financial products to help you succeed through financial service excellence
  • Options include loans, finance lease, operating lease, working capital, and revolving line of credit
  • Contact your local Cat dealer for availability in your region
Generator Set Specifications
Standby Rating1625/1600/1500 kVA
Prime Power Rating1500/1360 kVA
Emissions/Fuel StrategyLow Fuel, Low Emissions
Voltage380 to 415 Volts
Frequency50 Hz
Speed1500 rpm
Duty CycleStandby, Mission Critical, Prime
Maximum Rating1625 kVA
Minimum Rating1320 kVA
Engine Specifications
Engine Model3512B TA, V-12, 4-Stroke Water-Cooled Diesel
Bore6.69in
Stroke7.48in
Displacement3161.03in³
Compression Ratio14.0:1
AspirationTA
Fuel SystemElectronic Unit Injection
Governor TypeADEM™ A3
Generator Set Dimensions
Length - Minimum216.0in
Length - Maximum216.1in
Width - Minimum90.0in
Width - Maximum90in
Height - Minimum95.3in
Height - Maximum95.3in
Dry Weight - Genset (minimum)25038lb
Dry Weight - Genset (maximum)25677lb
Standard Equipment

Air Inlet System

  • Aingle element canister type air cleaner with service indicator

Air Inlet

  • Air cleaner

Cooling

  • Package mounted radiator (except C175)

Control Panel

  • Emergency stop button
  • Programmable protective relaying functions:
  • Over/under voltage (27 / 59)
  • kVAr (per phase, average & percent)
  • kVA (per phase, average & percent)
  • Engine cool-down timer
  • Generator mounted - rear facing
  • Overcurrent (50 / 51)
  • Warning/shutdown with common LED indication of shutdowns for:
  • Low coolant level
  • DC volts
  • Generator phase sequence
  • Overspeed
  • Frequency (Hz)
  • Volts (L-L & L-N)
  • Reverse reactive power (kVAr) (32RV)
  • Text alarm/event descriptions
  • 2 Programmable digital outputs
  • RPM
  • 2 Programmable relay outputs (Form C)
  • Speed adjust
  • Alarm acknowledge
  • kVAr-hr (total)
  • Digital indication for:
  • Power factor (per phase & average)
  • Environmental sealed front face
  • Controls:
  • True RMS AC metering, 3 phase, +/-2% accuracy
  • Low oil pressure
  • kW (per phase, average & percent)
  • Engine cycle crank
  • Accessory module data link
  • Coolant temperature
  • Cat ECS 100
  • 24 Volt DC operation
  • Over/under frequency (81 o/u)
  • Amps (per phase & average)
  • 4 Programmable relay outputs (Form A)
  • Reverse power (kW) (32)
  • Operating hours
  • Communications
  • Oil pressure (psi, kPa or bar)
  • Serial annunciator module data link
  • kW-hr (total)
  • 6 Programmable digital inputs
  • High coolant temperature
  • Failure to start (overcrank)
  • Low coolant temperature
  • Lamp test
  • Emergency stop
  • Auto/start/stop control
  • Customer data link (Modbus RTU)

Exhaust

  • Exhaust flange outlet

Fuel

  • Secondary fuel filters
  • Primary fuel filter with integral water separator
  • Fuel priming pump

Control System

  • Engine cool-down timer
  • DC volts
  • True RMS AC metering, 3-phase, +/-2% accuracy
  • High coolant temperature
  • Coolant temperature
  • Auto/start/stop control
  • Failure to start (overcrank)
  • Communications
  • Oil pressure
  • Emergency stop
  • Cat ECS 100
  • Overspeed
  • frequency (Hz)
  • Volts (L-L & L-N)
  • Engine cycle crank
  • Warnings/shutdown indicators
  • Speed adjust
  • Lamp test
  • 24 Volt DC operation
  • RPM
  • 4 programmable digital inputs
  • Low coolant level
  • Operating hours
  • Alarm acknowledge
  • Emergency stop pushbutton
  • Low oil pressure
  • Amps (per phase & average)
  • 4 programmable digital outputs
  • Digital indication for:

Generator

  • IP23 Protection
  • Matched to the performance and output characteristics of Cat engines

Power Termination

  • Busbar

Generator System

  • Class H temperature rise at 40C ambient
  • 3 phase brushless, Salient pole
  • 6 Lead
  • Winding temperature detectors
  • NEMA Class H insulation
  • Random wound
  • Internal excitation (IE)
  • 3-phase voltage sensing
  • Busbar connections
  • min/max exciter
  • Caterpillar's digital voltage regulator (CDVR)
  • RFI suppression

Literature

  • Parts book
  • Operation & Maintenance Manual

Cooling System

  • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
  • JWAC
  • Coolant level sensors (Not included with packages without radiator)
  • Coolant drain line with valve
  • Radiator fan and fan drive
  • Fan and belt guards

Exhaust System

  • Dry exhaust manifold
  • Flanged faced outlet(s)

Fuel System

  • Fuel priming pump
  • Secondary fuel filters
  • Fuel cooler; not included with packages without radiator
  • Flexible fuel lines - shipped loose

Generators and Attachments

  • Note: 1800 Frames are form wound, permanent magnet excitation (PMG), with winding temp detectors
  • 3 Phase voltage sensing
  • RFI suppression
  • Class H temperature rise at 40C ambient (125C prime / 150C standby)
  • Min / max exciter limiter
  • Exciter diode monitor
  • Busbar connections, top center mounted, top cable entry
  • 3 Phase brushless, Salient pole
  • 50 Hz models: IEC standard hole pattern
  • Caterpillar's digital voltage regulator (CDVR) includes:
  • Random wound
  • Generator set packages include: Regulator (CDVR)
  • Reactive droop capability
  • 6 Leads
  • KVAR / PF modes
  • NEMA Class H insulation
  • Winding temperature detectors
  • Internal excitation (IE)
  • LV

Governing System

  • Woodward 2301A isochronous governor

Lube System

  • Lubricating oil
  • Gear type lube oil pump
  • Integral lube Oil cooler
  • Oil filter, filler and dipstick
  • Fumes disposal
  • Oil drain lines and valve

Mounting System

  • Rails - Engine/generator/radiator mounting
  • Rubber anti-vibration mounts - shipped loose

Starting / Charging System

  • Battery disconnect switch
  • Battery and battery rack w/cables
  • 24 Volt electric starting motor

General

  • SAE standard rotation
  • Flywheel and Flywheel housing-SAE No. 00
  • RH service
  • Paint - Caterpillar yellow with high gloss black rails & radiator
Optional Equipment

Air Inlet System

  • Air inlet protection
  • Remote air inlet adaptors
  • Dual element air cleaners

Exhaust

  • Exhaust mufflers

Generator

  • Anti-condensation heater
  • Internal excitation (IE)
  • Permanent magnet excitation (PMG)
  • Oversize and premium generators

Circuit breakers

  • Cable entry options
  • 2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated Circuit breakers
  • Busbar connections
  • Center posts busbars
  • Controls packaging - Enclosures
  • 2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated Circuit breakers
  • Optional busbar power connections
  • EMAX breakers connections
  • EMAX Circuit breakers
  • Breaker harnesses

Power Termination

  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant

Control Panels

  • Annunciator modules
  • Customer connection mounting locations
  • Remote speed adjust
  • Local PC monitoring
  • Generator temperature monitoring
  • Auxiliary boxes
  • Governors
  • Customer interface options
  • EMCP 4.4
  • Ground (Automatically selected)
  • Mounting group - External box clips
  • Vandle proof panel door

Mounting

  • Rubber anti-vibration mounts
  • IBC isolators
  • Spring type vibration isolators

Starting/Charging

  • Oversize batteries
  • Air starting motor with control and silencer
  • Jacket water heater
  • Heavy duty starting system
  • Charging alternator
  • Battery chargers

Cooling System

  • Water level switch gauges
  • Optional radiator arrangements
  • Heat exchangers

European Certifications

  • European Union certification
  • EU Declaration of Conformity
  • European Directive genset, DoI (Declaration of Incorporation)
  • Eurasian Conformity (EAC) mark

Exhaust System

  • Mufflers
  • Muffler mounting kits
  • Through-wall installation kit
  • Flexible fittings

Fuel System

  • Primary fuel filter

Generators and Attachments

  • Generator conversion
  • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
  • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, Form wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
  • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, Internal excitation (IE), No. of leads = 6, pitch= 0.6667
  • Space heater

Instrumentation

  • Pyrometer and thermocouples

Lube System

  • Oil level reg-1 shallow pan
  • Electric prelube pumps
  • Manual prelube sump pumps

Mounting System

  • IBC vibration isolators
  • Spring type vibration isolators

Protection System

  • Explosion relief valves

Special Tests / Reports

  • PGS Test report @ 0.80 power factor
  • Neutral ground-LV
  • IBC seismic Certifications
  • PGS Test report @ 1.0 power factor
  • Neutral grounding connection

Starting / Charging System

  • Oversize battery set
  • Jacket water heaters
  • 10 Amp Battery chargers
  • Ether starting aid
  • 24 Volt dual electric starting motor
  • 20 Amp Battery charger

General

  • Engine barring group

Cat Switchgear

›
Cat Switchgear
ConfigurationIP4X
Operating Temperature35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)
Standard Widths600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A.