3512B (50 Hz) 1600 – 1875 kVA

3512B (50 Hz) Generator Set

THE RUNDOWN

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR5 Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
Cat ECS Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • IBC seismic certification
  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • EU Eurasian Conformity (EAC)
One Safe Source
  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Cat® Diesel Engine
  • Rugged, durable design with reliable performance proven in thousands of applications worldwide
  • Certified alternative fuels including Hydrotreated Vegetable Oil (HVO), Renewable Diesel (RD) and Hydrotreated Renewable Diesel (HRD) which meet EN 15940 or ASTM D975 can be used or blended with EN 590 diesel
Cat Generator Set Package
  • Accepts 100% block load in one step
  • Meets NFPA 110 loading requirements
  • Conforms to ISO 8528-5 G3 load acceptance requirements
  • Reliability verified through torsional vibration, fuel consumption, oil consumption, transient performance, and endurance testing
Alternators
  • Superior motor starting capability minimizes need for oversizing generator
  • Designed to match performance and output characteristics of Cat diesel engines
Cooling System
  • Cooling systems are available to operate in ambient temperatures up to 50°C (122°F)
  • Tested to ensure proper generator set cooling
Cat® Energy Control System (ECS)
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirements
  • Expansion modules and site specific programming for specific customer requirements
  • Graphical touchscreen display
  • Easily upgradeable
Warranty
  • 24 months/1000-hour warranty for Standby and Mission Critical ratings
  • 12 months/unlimited hour warranty for Prime and Continuous ratings
  • 12 months/unlimited hour warranty for Prime-DCP ratings
  • Extended service protection is available to provide extended coverage options
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Financing
  • Caterpillar offers an array of financial products to help you succeed through financial service excellence
  • Options include loans, finance lease, operating lease, working capital, and revolving line of credit
  • Contact your local Cat dealer for availability in your region
Generator Set Specifications
Standby Rating1875/1750 kVA
Prime Power Rating1700/1600 kVA
Emissions/Fuel StrategyLow Fuel, Low Emissions
Voltage380 to 415 Volts
Frequency50 Hz
Speed1500 rpm
Duty CycleStandby, Mission Critical, Prime
Maximum Rating1875 kVA
Minimum Rating1600 kVA
Engine Specifications
Engine Model3512B TA, V-12, 4-Stroke Water-Cooled Diesel
Bore6.69in
Stroke8.46in
Displacement3576in³
Displacement - HD3576in³
Compression Ratio15.5:1 HD
AspirationTA
Fuel SystemElectronic Unit Injection
Governor TypeADEM™ A3
Stroke - HD8.46in
Generator Set Dimensions
Length - Minimum224.8in
Length - Maximum224.8in
Width - Minimum90in
Width - Maximum90in
Height - Minimum95.3in
Height - Maximum95.3in
Dry Weight - Genset (minimum)27132lb
Dry Weight - Genset (maximum)27132lb
Standard Equipment

Air Inlet System

  • Aingle element canister type air cleaner with service indicator

Air Inlet

  • Air cleaner

Cooling

  • Package mounted radiator (except C175)

Control Panel

  • kVAr-hr (total)
  • Volts (L-L & L-N)
  • RPM
  • kW (per phase, average & percent)
  • Over/under voltage (27 / 59)
  • Environmental sealed front face
  • Controls:
  • Engine cool-down timer
  • Customer data link (Modbus RTU)
  • High coolant temperature
  • 2 Programmable digital outputs
  • Power factor (per phase & average)
  • 24 Volt DC operation
  • Overspeed
  • Alarm acknowledge
  • Lamp test
  • kW-hr (total)
  • Low coolant temperature
  • Emergency stop
  • Generator phase sequence
  • Auto/start/stop control
  • Cat ECS 100
  • Low oil pressure
  • Engine cycle crank
  • Programmable protective relaying functions:
  • Reverse power (kW) (32)
  • Generator mounted - rear facing
  • Digital indication for:
  • Overcurrent (50 / 51)
  • Warning/shutdown with common LED indication of shutdowns for:
  • kVA (per phase, average & percent)
  • Serial annunciator module data link
  • Emergency stop button
  • Reverse reactive power (kVAr) (32RV)
  • 6 Programmable digital inputs
  • Failure to start (overcrank)
  • Low coolant level
  • Communications
  • Coolant temperature
  • True RMS AC metering, 3 phase, +/-2% accuracy
  • Speed adjust
  • Oil pressure (psi, kPa or bar)
  • 4 Programmable relay outputs (Form A)
  • kVAr (per phase, average & percent)
  • Over/under frequency (81 o/u)
  • Operating hours
  • Accessory module data link
  • Text alarm/event descriptions
  • Amps (per phase & average)
  • DC volts
  • Frequency (Hz)
  • 2 Programmable relay outputs (Form C)

Exhaust

  • Exhaust flange outlet

Fuel

  • Primary fuel filter with integral water separator
  • Secondary fuel filters
  • Fuel priming pump

Control System

  • Failure to start (overcrank)
  • Auto/start/stop control
  • Cat ECS 100
  • Lamp test
  • Emergency stop pushbutton
  • 4 programmable digital inputs
  • Volts (L-L & L-N)
  • Low coolant level
  • Overspeed
  • frequency (Hz)
  • Engine cycle crank
  • DC volts
  • Coolant temperature
  • Alarm acknowledge
  • True RMS AC metering, 3-phase, +/-2% accuracy
  • Communications
  • 24 Volt DC operation
  • Engine cool-down timer
  • RPM
  • Warnings/shutdown indicators
  • Digital indication for:
  • Oil pressure
  • Low oil pressure
  • Amps (per phase & average)
  • Speed adjust
  • Emergency stop
  • 4 programmable digital outputs
  • Operating hours
  • High coolant temperature

Generator

  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection

Power Termination

  • Busbar

Generator System

  • Internal excitation (IE)
  • NEMA Class H insulation
  • Caterpillar's digital voltage regulator (CDVR)
  • Class H temperature rise at 40C ambient
  • 3-phase voltage sensing
  • Busbar connections
  • min/max exciter
  • Random wound
  • 3 phase brushless, Salient pole
  • RFI suppression
  • Winding temperature detectors
  • 6 Lead

Literature

  • Operation & Maintenance Manual
  • Parts book

Cooling System

  • Coolant drain line with valve
  • Radiator fan and fan drive
  • Fan and belt guards
  • JWAC
  • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
  • Coolant level sensors (Not included with packages without radiator)

Exhaust System

  • Dry exhaust manifold
  • Flanged faced outlet(s)

Fuel System

  • Flexible fuel lines - shipped loose
  • Secondary fuel filters
  • Fuel priming pump
  • Fuel cooler; not included with packages without radiator

Generators and Attachments

  • 6 Leads
  • Note: 1800 Frames are form wound, permanent magnet excitation (PMG), with winding temp detectors
  • Busbar connections, top center mounted, top cable entry
  • KVAR / PF modes
  • Internal excitation (IE)
  • Generator set packages include: Regulator (CDVR)
  • RFI suppression
  • Winding temperature detectors
  • NEMA Class H insulation
  • 50 Hz models: IEC standard hole pattern
  • Reactive droop capability
  • 3 Phase brushless, Salient pole
  • Exciter diode monitor
  • Min / max exciter limiter
  • Random wound
  • 3 Phase voltage sensing
  • LV
  • Class H temperature rise at 40C ambient (125C prime / 150C standby)
  • Caterpillar's digital voltage regulator (CDVR) includes:

Governing System

  • Woodward 2301A isochronous governor

Lube System

  • Lubricating oil
  • Fumes disposal
  • Integral lube Oil cooler
  • Oil drain lines and valve
  • Gear type lube oil pump
  • Oil filter, filler and dipstick

Mounting System

  • Rubber anti-vibration mounts - shipped loose
  • Rails - Engine/generator/radiator mounting

Starting / Charging System

  • 24 Volt electric starting motor
  • Battery and battery rack w/cables
  • Battery disconnect switch

General

  • Paint - Caterpillar yellow with high gloss black rails & radiator
  • RH service
  • SAE standard rotation
  • Flywheel and Flywheel housing-SAE No. 00
Optional Equipment

Air Inlet System

  • Dual element air cleaners
  • Remote air inlet adaptors
  • Air inlet protection

Exhaust

  • Exhaust mufflers

Generator

  • Internal excitation (IE)
  • Anti-condensation heater
  • Oversize and premium generators
  • Permanent magnet excitation (PMG)

Circuit breakers

  • Cable entry options
  • Optional busbar power connections
  • EMAX breakers connections
  • Center posts busbars
  • 2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated Circuit breakers
  • Breaker harnesses
  • 2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated Circuit breakers
  • Controls packaging - Enclosures
  • Busbar connections
  • EMAX Circuit breakers

Power Termination

  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant

Mounting

  • Rubber anti-vibration mounts
  • Spring type vibration isolators
  • IBC isolators

Control Panels

  • Annunciator modules
  • Generator temperature monitoring
  • Vandle proof panel door
  • Auxiliary boxes
  • Mounting group - External box clips
  • Ground (Automatically selected)
  • Remote speed adjust
  • Local PC monitoring
  • Customer connection mounting locations
  • EMCP 4.4
  • Governors
  • Customer interface options

Starting/Charging

  • Oversize batteries
  • Air starting motor with control and silencer
  • Heavy duty starting system
  • Jacket water heater
  • Charging alternator
  • Battery chargers

Cooling System

  • Water level switch gauges
  • Heat exchangers
  • Optional radiator arrangements

European Certifications

  • European Directive genset, DoI (Declaration of Incorporation)
  • EU Declaration of Conformity
  • European Union certification
  • Eurasian Conformity (EAC) mark

Exhaust System

  • Through-wall installation kit
  • Mufflers
  • Muffler mounting kits
  • Flexible fittings

Fuel System

  • Primary fuel filter

Generators and Attachments

  • Generator conversion
  • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
  • Space heater
  • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, Form wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
  • 1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, Internal excitation (IE), No. of leads = 6, pitch= 0.6667

Instrumentation

  • Pyrometer and thermocouples

Lube System

  • Oil level reg-1 shallow pan
  • Manual prelube sump pumps
  • Electric prelube pumps

Mounting System

  • IBC vibration isolators
  • Spring type vibration isolators

Protection System

  • Explosion relief valves

Special Tests / Reports

  • PGS Test report @ 0.80 power factor
  • PGS Test report @ 1.0 power factor
  • IBC seismic Certifications
  • Neutral ground-LV
  • Neutral grounding connection

Starting / Charging System

  • 24 Volt dual electric starting motor
  • Oversize battery set
  • Jacket water heaters
  • Ether starting aid
  • 20 Amp Battery charger
  • 10 Amp Battery chargers

General

  • Engine barring group