Cat® CBS Series

Cat® CBS – ATS with Bypass Isolation (Spec Grade)

THE RUNDOWN

Product Features
  • Advanced safety with faster switching and no line voltages connected at the door
  • Voltage and frequency sensing of both sources and load
  • USB port to upload/download settings
  • Available Bluetooth connection and enhanced communication capabilities
  • Password protection color touchscreen HMI
  • Integrated help button and menu
  • Five programmed packages and IO
  • Contact wear monitoring including real-time status and predicted contact end-of-life
  • Fast controller response to outage recovery and fast switching (<50ms)
Control Panel
  • TruOne L4 - color touchscreen HMI compatible with Ekip Connect software, with standard programmable functions and IO, and fast controller response to outage recovery and fast switching (<50ms).
Functions
  • High current protection and alarm
  • Wide 200-480V range with auto-configuration of system settings for 100-1200A range
  • High time-based withstand and closing ratings (WCR)
  • Short-time withstand ratings in every frame (CBS, CBSD, and CBSCT models)
Standards
  • UL 1008, NFPA 70, 99, 101 and 110
  • NEMA ICS 10
  • cUL
  • Conducted and radiated emissions - CISPR 11:2009, Class A
  • ESD immunity test - IEC/EN 61000-4-2 Class B
  • Radiated RF, electromagnetic field immunity test - IEC/EN 61000-4-3 10 V/m
  • Electrical fast, transient/burst immunity test - IEC/EN 61000-4-4
  • Surge immunity test - IEC/EN 61000-4-5 0.5 to 2 kV
  • Conducted immunity test - IEC/EN 61000-4-6
  • Voltage dips and interruption immunity - IEC/EN 61000-4-11
  • Harmonic voltage immunity test - IEC/EN 6100-4-13
Technical Summary
Rating Range100 - 3000 A
Transfer TypeOpen Transition (CBS), Delayed Transition (CBSD), Closed Transition (CBSCT), with Bypass Isolation
Switch TypeContactor
System Information
Product nodesUL: Open transition 100-3000A, Delayed transition 100-3000A, Closed transition 1000-3000A
Rated Voltage and Frequency200-480VAC, 50/60 Hz
Phase systemSingle and Three
Number of poles2, 3 and 4
Neutral configurationSolid neutral, Switched neutral, Overlapping neutral (100-1200A only)
Product typeOpen transition (I-II), Delayed Transition (I-O-II), Closed transition (I-O-II)
Standard Equipment

Control

  • Color touchscreen
  • Voltage and frequency settings: Pick up and Drop out
  • Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF (Delayed Transition Type), Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead.
  • Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence

Additional Features

  • LED indications for ATS, S1 and S2 status
  • Programmable digital inputs/outputs
  • Auto config (voltage, frequency, phase system)
  • Source priority (Source 1/2, No priority)
  • Manual re-transfer
  • In-phase monitor (synchro check)
  • Genset exercising: on-load, off-load
  • In-built power meter module
  • Load shedding
  • Real time clock
  • Event log
  • Predictive maintenance
  • Voltage and current harmonics measuring

Accessories

  • Auxiliary contacts for position indication
  • Digital input/output modules (factory programmed)
  • 12-24 VDC aux supply module for controller
  • Communication modules

Connectivity Capability

  • Modbus RTU (RS-485)
  • Modbus/TCP
  • Profibus DP
  • ProfiNet Yes
  • DeviceNet
  • Ethernet IP

Applications

  • Utility - Utility
  • Utility - Generator

UL short circuit withstand ratings

  • Coordinated breaker WCR
  • Time-based WCR
  • Short-time ratings
Optional Equipment

Options

  • Options not available