CN3586 Electric Motor for Gas Compression

CN3586 Electric Motor for Gas Compression

THE RUNDOWN

Electric Motor Specifications
Type of EX-ProtectionClass 1 Division 2 Group A,B,C,D T3 (NEC or CEC)
Mounting DesignationF1 or F2
Voltage/Frequency4000V & 4160V ± 10%/60 Hz
Full Load Speed894 rpm
Electric Motor TypeSquirrel Cage Induction Motor
Number of Poles8
Maximum Ambient Temperature104°F
Full Load Current458 Amps
Shaft8.5in
Rated Torque20555lb/ft
Maximum Altitude - Before Derate3300ft
Locked Rotor Amps540% Code E
Connection of Stator WindingStar
StandardsNEMA MG1
DutyContinuous
Enclosure Type/Method of CoolingWP-II
Locked Rotor Torque60%
Service Factor1.15 SF (1.0 VFD)
No Load Current137 Amps
InsulationClass F
Temperature RiseClass B at rated load
Standard Equipment

Bearings

  • Bearing RTDs for temperature monitoring
  • Insulated non-drive end bearings to reduce bearing currents
  • Anti-friction on 1500 hp (optional)

Rotors

  • Designed for minimal vibration
  • Dynamic balancing at full operational speed
  • Fabricated copper squirrel cages
  • Forged, keyless shaft
  • AISI 4140/DIN42CrMo4 shaft

Stators

  • Radial air ducts ensure uniform and efficient cooling
  • Vacuum pressure impregnated with specially formulated epoxy resin
  • 2X RTDS per Phase
  • Space heater
  • Welded and machined stator core retains its rigidity throughout motor life to ensure a sealed and homogeneous insulation system that results in high dielectric strength, excellent heat transfer and the elimination of hazardous internal partial discharges

CN1566 Electric Motor

CN1566 Electric Motor
Voltage/Frequency4000V ± 10%/60 Hz
Type of EX-ProtectionClass 1 Division 2 Group A,B,C,D T3 (NEC or CEC)
Mounting DesignationF1 or F2

CN5086 Electric Motor

CN5086 Electric Motor
Voltage/Frequency4000V ± 10%/60 Hz
Type of EX-ProtectionClass 1 Division 2, Group A,B,C,D T3 (NEC or CEC)
Electric Motor TypeSquirrel Cage Induction Motor

CN3086 Electric Motor for Gas Compression

CN3086 Electric Motor for Gas Compression
Voltage/Frequency4000V & 4160V ± 10%/60 Hz
Type of EX-ProtectionClass 1 Division 2 Group A,B,C,D T3 (NEC or CEC)
Mounting DesignationF1 or F2