Cat Switchgear

Cat Switchgear

THE RUNDOWN

Cat Switchgear
  • Independently certified to meet IEC 61439-2:2011 BS & international standard.
  • Standard ACB breaker range 1600A - 4000A CE & EAC marked.
  • Standard breaker fault rating 65 kA Icc, option for 100kA Icc ABB Emax 2 E4.
  • Certified assembly high fault rating, tested up to 100 kA / 1s ICW
  • Certified standard temperature rise tested.
  • Design verification to Annex D of IEC 61439-2:2011
  • Smaller footprint matched to the generator packaged design.
  • Innovative cableway management.
  • Modularity:
  • Built around 150mm modules in 3 axis.
  • Framework utilises a 25mm grid allowing a fully configurable system.
  • Easy to extend and upgrade.
  • Copper HDHC:
  • Standard 10mm copper with 10mm spacing improves heat rejection.
  • Stainless steel mounted busbar supports, reduce eddy currents.
  • Fully tinned option.
  • Breaker options:
  • Accommodates fixed or withdrawable breakers.
  • 3 or 4 pole option.
  • Manual or motorized option.
  • ACB door selection option.
  • Enclosure options: o Options up to Form 4b separation.
  • Configurable for top or bottom entry.
  • Swivel lifting eye (4 point lift) for single sections.
  • IP54 protection option.
  • 50 °C option.
  • Option to include generator controllers or PLC.
  • EPD white powder coated, option for custom colours.
  • In house automated routine testing.
  • Rating plate.
  • Cat warranty.
Enclosure Rating
ConfigurationIP4X
Operating Temperature
Operating Temperature35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F)
Dimensions
Standard Widths600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A.
Standard HeightsHeights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping
Standard Depths300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers
Technical Summary
Technical SummaryModular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers.
Application
ApplicationLV 380…480 VAC, 50 Hz, 3-Phase.
Modes of Operation
Modes of OperationSwitchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc.