MX350 Controller

MX350 Controller

The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, ...
PDF Print SHARE

Technical Summary

Rating Range
Switch Dependent
Transfer Type
Application Dependent
Switch Type
Application Dependent

Controller Specifications

Source Sensing
120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A)
Control Power
120 VAC
Communications Interface - Optional
Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T)
Undervoltage Dropout for Source 1 and Source 2
75-99% of nominal
Undervoltage Restore for Source 1 and Source 2
85-100% of nominal
Underfrequency Dropout for Source 1 and Source 2
45 - 59.9 Hz
Underfrequency Restore for Source 1 and Source 2
45 - 59.5 Hz
Overvoltage Dropout for Source 1 and Source 2
105 - 110% of nominal
Overvoltage Restore for Source 1 and Source 2
103 - 108% of nominal
Overfrequency Dropout for Source 1 and Source 2
50.1 - 63 Hz
Overfrequency Restore for Source 1 and Source 2
50 - 62.9 Hz
Voltage Unbalance on Dropout for Source 1 and Source 2
5 to 20% of nominal
Voltage Unbalance for Restore for Source 1 and Source 2
4 to 19% of nominal
Load Control Relay Contacts (1)
rated for 10A @ 24VDC or 120VAC
Load Control Relay Contacts (2)
0-259 minutes
Delay for Engine Cool Down (U)
0-60 minutes
Delay Transfer to Nonpreferred Source (W)
0-5 minutes
Delay NeutralTransition Time Delays (DT,DW)
0-10 minutes
Storage Temperature
(-40?C - 90?C )
Operating Temperature Ambient
(-20?C to 50?C)

Standard Equipment:

Optional Equipment:

    Option Package A:
    • Full function ATS control with full sensing and control capabilities
    • Expanded diagnostics, high-speed 256 event capture, 365 days
    • Monitoring Software (local or remote), USB interface for uploading and downloading setup parameters
    • Four (4) programmable inputs and four (4) outputs assignable to additional ATS features
    • Full complement of programmable ATS control switches AUTO / MAN, Preferred Source selector,Commit / No Commit Xfer, Transition Mode Select for Closed Transition switch models)
    Option Package B:
    • Includes Option Package A features, plus
    • Ten (10) customer programmable digital and ten (10)analog alarms.
    • Twenty (20) channel data logger, customer configurable sample period from one (1) cycle to sixty (60) minutes.
    • Waveform capture, ten (10) channels, up to 256 cycles each sixteen (16) samples / sec.
    • Auto Load Shed with voltage, frequency and kW triggers.
    Option Package C:
    • Includes Option B features, plus
    • Four (4) additional inputs and outputs (totaling eight (8) in & eight (8) out)
    Option Package D:
    • Includes Option Package C features, plus
    • Four (4) additional inputs and outputs (totaling twelve (12) in & twelve (12) out)
    • Customized user control logic
    Option Package M:
    • Configuration for Manual Operation only (Non-Automatic)