G3512E Gas Generator Set

G3512E Gas Generator Set

PDF Print Share

Generator Set Specifications

Continuous Rating
1200 ekW
Fuel Type
Natural Gas
Maximum Electrical Efficiency
42.30%
Maximum Standby Rating
-
Frequency
50 Hz
Speed
1500 rpm

Generator Set Dimensions

Length
181in
Width
65in
Height
89in
Dry Weight - Genset
27475lb

Engine Specifications

Engine Model
G3512E
Bore
6.7in
Stroke
7.5in
Displacement
3158in³
Aspiration
TA

Cat G3512E Gas Engine

  • Robust high speed block design provides prolonged life and lower owning operationg costs
  • Designed for maximum performance on low pressure pipeline natural gas
  • Simple open chamber combustion system for reliability and fuel flexibility
  • Leading edge technology in ignition system and air/fuel ratio control for lower emission and engine efficiency
  • One electronic control module handles all engine functions: ignition, governing, air/fuel ratio control and engine protection

SR4B Generator

  • Designed to match performance and output characteristics of Caterpillar gas engines
  • Industry leading mechanical and electrical design
  • High efficiency

EMCP 4.3 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cat Electronic Control System

  • Simple user friendly interface and navigation
  • Digital monitoring, metering and protection setting
  • Fully-featured power metering and protective relaying
  • Remote control and monitor capability options

Cooling System

Emissions

  • Meets most worldwide emissions requirements down to 0.5 g/bhp-hr NOx level without aftertreatment

Proven System

  • Field proven in a wide range of applications worldwide
  • Fully prototype tested
  • Certified torsional vibration analysis available

Full Range of Attachments

  • Wide range of bolt-on system expansion attachments
  • Factory designed and tested
  • Flexible packaging options for easy and cost effective installation

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment:

Optional Equipment:

    Air Inlet
    • Mounting brackets and piping
    • Air cleaner with precleaner
    Circuit Breakers
    • Frame mounting
    • Right, left, rear mounted
    • 3-pole (IEC 947-2 rated)
    • 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
    • S LSI, G LSIG, P LSIG-P, 4th Digit Type
    • 1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
    • 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
    • 2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
    Cooling
    • Remote radiator for JW and SCAC circuits, level switch included but not wired
    • Coolant level drain line with valves, fan with guard
    • Inlet/Outlet connections
    Control Panel
    • Local alarm module
    • Remote annunciator
    • Local PC monitoring
    • Remote PC monitoring
    • Engine failure relay
    Exhaust
    • 305 mm (12 in.) Flange
    • 250mm-329mm Flange Expander
    • Flexible fittings
    Fuel System
    • Remote mounted gas train, sized for 31.5 MJ/Nm3 (800 btu/cu ft) dry pipeline natural gas with inlet pressure range of 19.2 to 48.3 kPa (2.78 to 7 psi).
    General
    • US AID emblem
    • Special paint order
    • Tool set
    • Digital diagnostic tool
    Generator
    • Cable access box
    • Bearing temperature detectors
    • Generator air filter
    • European bus bars
    Starting/charging
    • 24V starting motors
    • Battery with cables and rack (shipped loose)
    • Jacket water heater
    • 45A, 24V charging alternator (requires engine driven pumps)
    • 20A, 24VDC battery charger