C32 (50 Hz) with Upgradeable Packaging

C32 (50 Hz) with Upgradeable Packaging

The C32 with the upgradeable packaging design has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. ...
PDF Print SHARE

Generator Set Specifications

Minimum Rating
910 kVA
Maximum Rating
1500 kVA
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Voltage
400 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Mission Critical, Prime, Continuous

Engine Specifications

Engine Model
C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
5.71in
Stroke
6.38in
Displacement
1958.9in³
Compression Ratio
15.0:1
Aspiration
TA
Fuel System
MEUI
Governor Type
Adem™A4

Generator Set Dimensions

Length - Minimum
165.3in
Length - Maximum
179.2in
Width - Minimum
66.3in
Width - Maximum
87.8in
Height - Minimum
85.1in
Height - Maximum
85.6in
Dry Weight - Genset (minimum)
14680lb
Dry Weight - Genset (maximum)
17855lb

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • EU Certification of as Conformance (CE)

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment:

Optional Equipment:

    Control System
    • Expansion I/O module
    • EMCP 4.3, EMCP 4.4
    • Remote annunciator module
    • Remote monitoring software
    • Local annunciator module
    • Remote annunciator module
    • EMCP (4.2) (4.3) (4.4)
    • Local annunciator module
    Engine Options
    • Radiator duct flange
    • Exhaust guards / shields
    • Heavy duty electric starting motors
    • Dual element air cleaners
    • Heavy duty air cleaners
    • Muffler (industrial grade)
    Engine System
    • Heavy duty electric starting motors
    • Battery charger (10 amps)
    • Spring type anti-vibration mounts (95% efficient)
    • Heavy duty batteries
    • Heavy duty air cleaners
    • Dual element air cleaners
    • Exhaust guards / shields
    • Muffler (industrial grade)
    • Radiator duct flange
    • Jacket water heater
    • Rubber anti-vibration mounts (90% efficient)
    Extended Service Contract
    • 2 Year Extended Service Contract (ESC)
    • 3 Year Extended Service Contract (ESC)
    • 5 Year Extended Service Contract (ESC)
    Generators
    • Anti-condensation heaters
    • Winding: [ ] Random [ ] Random with coastal insulation [ ] Form
    • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
    • Temperature Rise over 40°C ambient: [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
    • Generator stator and bearing temperature monitoring & protection
    • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
    • Winding: [ ] Random [ ] Random with coastal insulation [ ] Form
    • Temperature Rise over 40°C ambient: [ ] 150°C [ ] 125°C [ ] 105°C [ ] 80°C
    Power Termination
    • Circuit breaker, IEC listed (fully rated)
    • Bus bars
    • Circuit breaker, 100% Rated, UL Listed (fully rated)